Technical Data

SMA Solar Technology AG

102

SCxxxHE-IEN104432

Installation Guide

8.3 Sunny Central 630HE-11

Input parameters

*Specifications apply to irradiation values below STC

Output data

Efficiency

Mechanical data

Power consumption

* Internal consumption measured in clock-rate operation with activated AC fans, activated DC fans and power unit cooling unit at

100 % Minimum connected load per phase < 1 500 W

Nominal power DC

P

PV

642 kWp

Maximum PV power (recommended)*

P

PV

705 kWp

Maximum input voltage

U

DC max

1 000 V

DC voltage range, MPPT

U

DC

500 V – 820 V

Maximum input current

I

DC, max

1 422 A

Voltage ripple

Upp

< 3 %

Number of non-fused connection points /
maximum number of fused DC inputs

2 ports for external DC main
distributions (Sunny Main Box) /
8 per potential

Nominal AC output

P

ACNom

630 kW

Operational voltage ±10 %

U

ACNom

315 V

Nominal output current

I

ACNom

1 155 A

Nominal operating frequency

f

ACNom

50 Hz / 60 Hz

Total harmonic distortion of output current at
nominal output power

K

IAC

< 3 %

Power factor

cos φ

90 leading / 90 lagging

Max. efficiency

h

max

98.6 %

European efficiency

h

euro

98.4 %

Width x height x depth in (W x H x D)

1 600 + 1 200 mm x 2 120 mm x 850 mm

Weight: approx.

1 900 kg

Internal consumption in operation*

P

day

< 1 500 W

Internal consumption in night mode

P

night

< 100 W

Internal power supply / grid structure

3 x 400 V, 50 / 60 Hz, TN-S grid /
TNC grid / TT grid

External pre-fuse for internal power supply

B 20 A, 3 pol.

Advertising