2 checking the sunny central cabling, 1 checking internal connections, 2 checking the ac grid connection – SMA SC 400HE Installation User Manual

Page 91: Checking the sunny central cabling, Checking internal connections, Checking the ac grid connection

Advertising
background image

SMA Solar Technology AG

Commissioning

Installation Guide

SCxxxHE-IEN104432

91

7.2 Checking the Sunny Central Cabling

All electrical connections made on-site must be checked for correct connection and secure attachment.

7.2.1 Checking Internal Connections

• Check that the plugs of the transfer terminal strip are in the correct sequence and are securely

in place.

• Check that the transformer or sinusoidal filter connections are securely in place and have the

correct phase sequence.

• Check that the data and control lines are correctly connected to the power unit.
• Check that the data line for insulation monitoring is correctly connected.
• Check the installation location of the internal temperature sensor.
• Check the internal power cabling of the team connection (optional).
• Check the connection between the PE rails of the partial barrier.

7.2.2 Checking the AC Grid Connection

• Check the connections to ensure that they are securely in place.
• Check the phase sequence.
• Check the correct connection in accordance with the circuit diagram.
• Check the PE-N bridge for the grid structure TN-C or TN-S on-site and remove it if necessary.
• Check the correct installation of the covers. Correct installation means that contact protection is

guaranteed.

Equipotential Bonding

• Check whether the Sunny Central is connected to the equipotential bonding of the installation

site.

• Check that the connections are secure.

Checking connections
See the documentation provided and the circuit diagram for the precise electrical
connections.
In particular, note the following points:

• Misconnections.
• Incorrect polarity, in particular for power connections.

Make sure that everything is securely in place.

• Check that the connections have been tightened. Where possible, avoid retightening

in accordance with the torque specifications in the circuit diagram.

• Only retighten connections according to the torque specifications in the circuit

diagram if they are loose.

Advertising
This manual is related to the following products: