Installation Guide

Air Quality Classification for Chemically Active Substances

Environmental conditions for stationary
application

Class
3C1R 3C1L 3C1 3C2 3C3 3C4

a) Marine salt

-

-

-

Occurrence of marine
salt

b) Sulfur dioxide, mg / m³

0.01

0.1

0.1

1.0

10

40

c) Hydrogen sulfide, mg / m³

0.0015 0.01

0.01

0.5

10

70

c) Chlorine, mg / m³

0.001

0.01

0.1

0.3

1.0

3.0

d) Hydrogen chloride, mg / m³

0.001

0.01

0.1

0.5

5.0

5.0

e) Hydrogen fluoride, mg / m³

0.001

0.003 0.003 0.03

2.0

2.0

f) Ammonia, mg / m³

0.03

0.3

0.3

3.0

35

175

g) Ozone, mg / m³

0.004

0.01

0.01

0.1

0.3

2.0

h) Nitrogen oxides, mg / m³

0.01

0.1

0.1

1.0

9.0

20

Installation sites with carefully monitored and
regulated atmospheres (category clean
spaces).

x

x

x

x

x

x

Installation sites with carefully regulated
atmospheres.

x

x

x

x

x

Installation sites in rural or densely populated
areas with little industry and moderate traffic
volume.

x

x

x

x

Installation sites in densely populated areas
with industry and high traffic volume.

x

x

x

Installation sites directly neighboring industrial
plants, with chemical emissions.

x

x

Installation sites directly inside of industrial
plants, with emission of high concentrations of
chemical pollutants.

x

Environmental Conditions
The following points must be observed in relation to environmental conditions:

• Required amount of fresh air
• Stipulated air quality
• Relative humidity
• Permissible ambient temperature