Terminal board set-up comparison, 6 main control pcb comparison, Table 6 factory default functions 2-wire control – Yaskawa GPD515/G5 User Manual

Page 11

Advertising
background image

6 Main Control PCB Comparison

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

11

‹

Terminal Board Set-Up Comparison

Figure 1

Figure 1 GPD515/G5 Terminal Board Configuration

Figure 2

Figure 2 A1000 Terminal Board Configuration

Table 6 Factory Default Functions 2-Wire Control

GPD515/G5 Terminal

A1000 Terminal (Designations similar to GPD515/G5)

Type

GPD515/G5 Terminal

Default Functions

A1000 Terminal

Default Function

A1000 Description

Digital Input Signals

1

Forward run/stop
Signal level:
(Photo-coupler insulated
Input: +24 Vdc, 8 mA)

S1

Forward run/stop command

Multi-function inputs 1-8
Photocoupler
24 Vdc, 8 mA
Set the S3 jumper to select
between sinking, sourcing
mode, and the power supply.

2

Reverse run/stop

S2

Reverse run/stop command

3

External fault input

S3

External fault input

4

Fault reset input

S4

Fault reset

5

Master/Auxilary change
Multi-step speed reference 1

S5

Multi-step speed reference 1
(Master/auxiliary switch)

6

Multi-step speed reference 2

S6

Multi-step speed reference 2

7

Jog reference

S7

Jog frequency reference

8

External baseblock

S8

External baseblock N.O.

11

Sequence control input
common

SN

Digital input common

Multi-function input
common

SC

Factory connected to SP

24 Vdc Power Supply for
Digital inputs, 150 mA max
(only when not using digital
input option DI-A3)

SP

Factory connected to SC

Advertising