YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

10 Appendix 2 Parameter Cross Reference

10

Appendix 2 Parameter Cross Reference

‹

Parameter Compatibility Table

1.

This document lists the information needed to upgrade from G5 to a new A1000 drive. The A1000 drive must be set for Heavy Duty. First, set A1000
parameter C6-01 to 0.

2.

Check all G5 parameters that have been changed from their default settings by using the Modified Constants Menu.

3.

Set the same control mode used for G5 to A1000.

4.

Set parameters as described in this section.

Note: Default Values in the table below are listed for A1000 240 V Class 0.4 kW Drive Using Open Loop Vector Control.

Table 23 Parameter Cross Reference

Parameter Name

G5

A1000

Comments (Gray shading indicates default settings)

No.

Default

No.

Default

G5

A1000

Environment Settings

Language Selection for
digital operator display

A1-00

0

A1-00

0

A1-00

A1-00

0: English

0: English

1: Japanese

1: Japanese

2: German

2: German

3: French

3: French

4: Italian

4: Italian

5: Spanish

5: Spanish

6: Portuguese

6: Portuguese

7: Chinese

Constant Access Level

A1-01

2

A1-01

2

A1-01

A1-01

0: Monitor Custom

0: Operation only
(monitors only)

1: User Selection Parameter

1: User Parameters *

2: QUICK-START (Q)

2: All parameters

3: BASIC (B)
4: ADVANCED (A)
* A2-01 through A2-32 Setting

User setting constant

A1-02

2

A1-02

2

A1-02

A1-02

0: V/f

0: V/f Control

1: V/f w/PG Control

1: V/f w/PG Control

2: Open Loop Vector

2: Open Loop Vector

3: Flux Loop Vector

3: Closed Loop Vector

5: Open Loop Vector for PM

6: Advanced Open Loop Vector
Control for PM

7: Closed Loop Vector Control
for PM

Initialize

A1-03

0

A1-03

0

A1-03

A1-03

0: No initialization

0: No initialization

1110: User Setting

1110: User initialize

2220: 2-wire sequence

2220: 2-wire sequence

3330: 3-wire sequence

3330: 3-wire sequence

5550: Reset OPE04

Enter Password

A1-04

0

A1-04

0000

Password 2

A1-05

0

A1-05

0000

User setting constant

A2-01 to

A2-32

A2-01 to

A2-32

If setting A1-01 to 1, refer to the manual and set parameters A2-01
to A2-32.