11 Appendix 3 Terminal Size and Wire Gauge

74

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

Table 28 Control Circuit Terminal Size and Wire Gauge

A1000

5A0192

R/L1, S/L2, T/L3

U/T1, V/T2, W/T3

-, +1, +2

B1, B2

G5

5160

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3, -, +3

M4

180 to 200

(350 to 400)

Pressure

Lug

30 to 60

(3 to 2/0)

r,

M4

2 to 5.5

(14 to 10)

A1000

5A0242

R/L1, S/L2, T/L3

U/T1, V/T2, W/T3

-, +1, +2

B1, B2

Power Supply

Series

Capacity

Terminal Signal

Terminal Screw

Tightening Torque

(N m)

Wire Range

AWG

(mm

2

)

Recommended

Gauge

AWG

(mm

2

)

200 V Class
400 V Class

G5

All capacities

1 to 11, 13 to 33

M3.5

Stranded wire:

0.5 to 1.25

Single Line

0.5 to 1.25

12 (G)

M3.5

0.5 to 2.0

200 V Class
400 V Class

A1000

All capacities

FM, AC, AM, P1,
P2, PC,
SC, SN, SP, A1, A2,
A3, +V, -V,
S1, S2, S3, S4, S5,
S6,S7, S8,
MA, MB, MC, M1-
M6

Phoenix type

4.2 to 5.3

(0.5 to 0.6)

Stranded wire:

26 to 16

(0.14 to 1.5)

18

(0.75)

MP, RP, R+, R-, S+,
S-, IG
DM+, DM-, H1, H2,
HC

Phoenix type

4.2 to 5.3

(0.5 to 0.6)

Stranded wire:

26 to 16

(0.14 to 1.5)

18

(0.75)

E (G)

M3.5

7.0 to 8.8

(0.8 to 1.0)

20 to 14

(0.5 to 2.0)

12

(1.25)

Series

Model

Terminal Signal

Terminal

Screw

Tightening Torque

N m (lb.in.)

Possible Gauges

mm

2

(AWG/kcmil)

Recommended

Gauge mm

2

(AWG/

kcmil)

Advertising