10 Appendix 2 Parameter Cross Reference
40
YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide
PDI Control
PID Control Method 
Selection
b5-01
0
b5-01
0
b5-01
b5-01
0: Disabled
0: Disabled
1: D = control for bias
1: D control for bias
2: D control of feedback
2: D control of feedback
3: D control of Freq. Ref. + PID 
output bias
3: D control of Freq. Ref. + PID 
output bias
4: D control of Freq. Ref. + PID 
output
4: D control of Freq. Ref. + PID 
output
Proportional Gain 
Setting (P)
b5-02
1.00
b5-02
1.00
─
Integral Time Setting 
(I)
b5-03
1.0 s
b5-03
1.0 s
─
Integral Limit Setting
b5-04
100.0 %
b5-04
100.0 %
─
Derivative Time (D)
b5-05
0.00 s
b5-05
0.00 s
─
PID Output Limit
b5-06
100.0 %
b5-06
100.0 %
─
PID Offset adjustment
b5-07
0.0 %
b5-07
0.0 %
─
PID Primary Delay 
Time
b5-08
0.00 s
b5-08
0.00 s
─
PID Output 
Characteristics 
Selection
b5-09
0
b5-09
0
b5-09
b5-09
0: FWD
0: FWD
1: REV
1: REV
PID Output Gain 
Setting
b5-10
1.0
b5-10
1.00
Minimum setting units vary.
PID Output Reverse 
Selection
b5-11
0
b5-11
0
b5-11
b5-11
0: Negative PID output triggers 
zero limit
0: Negative PID output triggers 
zero limit
1: Rotation direction reverses 
with negative PID output.
1: Rotation direction reverses 
with negative PID output.
Selection PID 
Feedback Command 
Loss Detection
b5-12
0
b5-12
0
b5-12
b5-12
0: No Detection
0: No Detection
1: Continue operation
1: Continue operation
2: Fault
2: Fault
─
3: Multi-function output only 
detected during PID control 
cancel input only.
─
4: An alarm is triggered and the 
drive continues running. 
Detected only when PID control 
is canceled.
─
5: Fault is triggered and output 
is shut off. Detected only when 
PID control is canceled.
PID Feedback 
Command Loss 
Detection Level
b5-13
0 %
b5-13
0 %
─
PID Feedback 
Command Loss 
Detection Time
b5-14
1.0 s
b5-14
1.0 s
─
Dwell Function
Dwell Reference at 
Start
b6-01
0.0 Hz
b6-01
0.0 Hz
─
Dwell Time at Start
b6-02
0.0 s
b6-02
0.0 s
─
Dwell Frequency at 
Stop
b6-03
0.0 Hz
b6-03
0.0 Hz
─
Dwell Time at Stop
b6-04
0.0 s
b6-04
0.0 s
─
Droop Control
Droop Control Gain
b7-01
0.0 %
b7-01
0.0 %
─
Droop Control Delay 
Time
b7-02
0.05 s
b7-02
0.05 s
─
Energy Saving Control
Energy Saving Gain
b8-01
80 %
b8-01
0
b8-01
b8-01
Enabled via multi-function 
input ( H1-XX=63)
0: Disabled
Not available 
in A1000
b8-02
0.7
1: Enabled
Divide the 
setting of
b8-01 in G5 
by 100
Energy Saving 
Frequency
b8-02
0.0 Hz
―
―
This parameter is not available in A1000, and therefore does not 
need to be set.
Parameter Name
G5
A1000
Comments (Gray shading indicates default settings)
No.
Default
No.
Default
G5
A1000