10 Appendix 2 Parameter Cross Reference

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

43

V/f Characteristics

Input Voltage Setting

E1-01

230 V*

E1-01

230 V*

*Double this value for 400 V class drives.Multiply by three
for 600 V class drives.

Motor selection

E1-02

0

L1-01

1*

E1-02

L1-01

L1-01

0: Disabled

0: Disabled

0: General-
purpose motor
protection

1: Enabled

1: General-purpose motor
protection

1: Drive-
dedicated
motor
protection

2: Drive-dedicated motor
protection

Motor Protection
function selection

L1-01

1

2: Vector
motor
protection

3: Vector motor protection

4: PM motor protection
(derated torque)

5: PM motor protection
(constant torque)

6: General Purpose motor
(50 Hz)

* Determined by the control mode selected

Parameter Name

G5

A1000

Comments (Gray shading indicates default settings)

No.

Default

No.

Default

G5

A1000