10 appendix 2 parameter cross reference – Yaskawa GPD515/G5 User Manual

Page 54

Advertising
background image

10 Appendix 2 Parameter Cross Reference

54

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

Analog Input

Gain (terminal 14)
(terminal A2 for
A1000)

H3-10

100.0 %

H3-11

100.0 %

Bias (terminal 14)
(terminal A2 for
A1000)

H3-11

0.0 %

H3-12

0.0%

Analog Input Filter
Time Constant

H3-12

0.03 s

H3-13

0.03 s

Analog Input Terminal
Enable Selection

H3-14

7

H3-14

1: Terminal A1 enabled

2: Terminal A2 enabled

3: Terminals A1, A2 enabled

4: Terminal A3 enabled

5: Terminals A1, A3 enabled

6: Terminals A2, A3 enabled

7: Terminals A1, A2, and A3
enabled

Multi-Function Analog
Output

Monitor Selection
(terminal 21) (terminal
FM for A1000)

H4-01

2*

H4-01

102*

*Refer to the “Comments” column for F4-01

Gain (terminal 21)
(terminal FM for
A1000)

H4-02

1.00

H4-02

100.0 %

Setting units differ between G5 and A1000.
Set A1000 by multiplying H4-05 in G5 by 100.

Bias (terminal 21)
(terminal FM for
A1000)

H4-03

0.0 %

H4-03

0.0 %

Monitor Selection
(terminal 23) (terminal
FM for A1000)

H4-04

3*

H4-04

103*

*Refer to the “Comments” column for F4-01

Gain (terminal 23)
(terminal FM for
A1000)

H4-05

0.50

H4-05

50.0 %

Setting units differ between G5 and A1000.
Set A1000 by multiplying H4-05 in G5 by 100.

Bias (terminal 23)
(terminal FM for
A1000)

H4-06

0.0 %

H4-06

0.0 %

Multi-Function Analog
Output Signal Level
Selection

H4-07

0

H4-07

(FM monitor)

0

H4-07

H4-07

Terminal FM

Signal Level

Selection

H4-08

Terminal AM

Signal Level

Selection

0: 0 to +10 V output

0: 0 to 10 V

H4-08

(AM monitor)

0

1: 0 to ±10 V output

1: -10 to 10 V

2: 4 to 20 mA

MEMOBUS
Communication

Station Address

H5-01

1F

H5-01

1F

Communication Speed
Selection

H5-02

3

H5-02

3

H5-02

H5-02

0: 1200 bps

0: 1200 bps

1: 2400 bps

1: 2400 bps

2: 4800 bps

2: 4800 bps

3: 9600 bps

3: 9600 bps

4: 19200 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Communication Parity
Selection

H5-03

0

H5-03

0

H5-03

H5-03

0: No parity

0: No parity

1: Even parity

1: Even parity

2: Odd parity

2: Odd parity

MEMOBUS
Communication

Stopping Method After
Communication Error

H5-04

3

H5-04

0

H5-04

H5-04

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Alarm Only

3: Alarm Only

Communication Error
Detection Selection

H5-05

1

H5-05

0

H5-05

H5-05

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Parameter Name

G5

A1000

Comments (Gray shading indicates default settings)

No.

Default

No.

Default

G5

A1000

Advertising