Power-up diagnostics, 4 option components – Yaskawa APOGEE FLN P1 User Manual
Page 12

Name
Display
Operating Status
Remarks
Color
Status
RX
-
OFF
No data seen on the network The option is not physically connected to the
network or there is no network activity.
Green
Flashing
Data is seen on the network The option is connected to a network.
n
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may
take several seconds. After the LEDs have completed the diagnostic LED sequence, the option
is successfully initialized. The LEDs then assume operational conditions as shown in
Table 4 Power-Up Diagnostic LED Sequence
Sequence
Time
Module Status (MS)
Network Status (NS)
Tx
Rx
1
Initial
OFF
OFF
OFF
OFF
2
0.25 seconds
Green
OFF
OFF
OFF
3
0.25 seconds
Red
OFF
OFF
OFF
4
0.25 seconds
OFF
Green
OFF
OFF
5
0.25 seconds
OFF
Red
OFF
OFF
6
0.25 seconds
OFF
OFF
Green
OFF
7
0.25 seconds
OFF
OFF
OFF
Green
8
Run Time
Go to proper state
Go to proper state
Go to
proper state
Go to
proper state
4 Option Components
12