Yaskawa APOGEE FLN P1 User Manual

Page 45

Advertising
background image

The mailbox will write the value to the drive when this point is written. An ENTER or

ACCEPT command does not need to be sent for the data to be taken by the drive. The behavior

of the write is the same as with the digital operator. There are a limited number of drive

parameters that can be written if the drive is running.
Example: Writing a value of 387 (183H) to Point #72 specifies drive parameter b1-04. Writing

a value of 1 to Point #73 enables the drive for reverse run.

10 APOGEE FLN P1 Communications

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual

45