Apogee fln p1 communications, Slope and intercept conversion, Drive controlled feedback – Yaskawa APOGEE FLN P1 User Manual

Page 36: 10 apogee fln p1 communications, Conversion example

Advertising
background image

10

APOGEE FLN P1 Communications

u

Slope and Intercept Conversion

Several drive parameters are available for monitoring purposes. The available parameters include

FREQ OUTPUT (Point 3), SPEED (Point 5), CURRENT (Point 6), TORQUE (Point 7), POWER

(Point 8), DRIVE TEMP (Point 9), KWH (Point 10), and RUN TIME (Point 12). These points can

be unbundled for monitoring or used in various global control strategies

.

u

Drive Controlled Feedback

The most typical application is Supervisory Control. The sensor for the control variable (e.g.,

water temperature) is hard-wired to the drive and the control device (fan) is modulated using

the PI control loop built into the drive. The setpoint for the control variable (water temperature

set point) is unbundled and commanded by the field panel, based on the building control

strategy implemented in PPCL.
The point to unbundle and command for the set point is INPUT REF 1 (Point 60) when this

strategy is used. The control variable (e.g., water temperature) can be monitored by unbundling

PI FEEDBACK (Point 62). These points are provided in units of percent, where 0% and 100%

correspond to the range of the sensor being used to measure the control variable. These points

have default units in Hz. Unbundle these points with appropriate slopes and intercepts if other

units are required. The new intercept will be equal to the lowest value of the desired range.

The following formulas allow the user to define a new slope and intercept to convert the unit.
The following formulas allow the user to define a new slope and intercept to convert the unit.

(Desired Range) x (Slope of Existing Point)

(Range of Existing Point)

New Slope =

(60 - 0) Hz x (0.01)

(100 - 0)%

New Slope =

= 0.006

n

Conversion Example

The drive is controlling a fan, which in turn is controlling the water temperature from a cooling

tower. The temperature sensor has a range of -1 °C to +121 °C (30 °F to 250 °F). To unbundle

the set point (INPUT REF 1), for commanding in degrees Fahrenheit, where 0 to 60 Hz is equal

to -1 °C to +121 °C: New Intercept=30 (the temperature that corresponds to 0%).

(Desired Range) x (Slope of Existing Point)

(Range of Existing Point)

New Slope =

(250 - 30) °F x (0.1)

(100 - 0)%

New Slope =

= 0.22

Note:

1. Desired Range=Range Maximum - Range Minimum
2. Range of Existing Point=Existing Range Maximum - Existing Range Minimum

10 APOGEE FLN P1 Communications

36

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual