10 apogee fln p1 communications – Yaskawa APOGEE FLN P1 User Manual

Page 39

Advertising
background image

Information to consider when referencing this table:
1.

Points not listed are not used in this application.

2.

A single value in a column means that the value is the same in English units and in SI

units.

3.

Point numbers that appear in bold type (e.g. 03) can be unbundled at the field panel.

Table 15 APOGEE FLN P1 Application 2721 Point Number Summary

Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Parameter

01

LAO

CTLR ADDRESS

31

-

1

0

-

-

F6-78

02

LAO

APPLICATION

-

-

1

0

-

-

-

03

LAI

FREQ OUTPUT

0

Hz

0.01

0

-

-

U1-02

04

LAI

PCT OUTPUT

0

%

0.01

0

-

-

-

05

LAI

SPEED

0

RPM

1

0

-

-

-

06

LAI

CURRENT

0

A

0.01

0

-

-

U1-03

07

LAI

TORQUE

0

%

0.1

0

-

-

U1-09

08

LAI

POWER

0

kW

0.1

0

-

-

U1-08

09

LAI

DRIVE TEMP

0

° C/F

1

0

-

-

U4-08

10

LAI

DRIVE KWH

0

kWh

0.1

0

-

-

U4-10

11

LAI

MWH

0

MWh

1

0

-

-

U4-11

12

LAI

RUN TIME

0

h

1

0

-

-

U4-01

13

LAI

DC BUS VOLT

0

V

1

0

-

-

U1-07

14

LAI

AC OUT VOLT

0

V

0.1

0

-

-

U1-06

15

LAI

PAR N9.01

0

A

0.01

0

-

-

n9-01

16

LAI

RUN TIMEX10K

0

10Kh

1

0

-

-

U4-01

17

LAI

FAULT CODE

0

-

1

0

-

-

U2-01

18

LDI

MINOR FLT

NO FLT

-

1

0

FAULT

NO FLT

U1-12

(Bit 6)

19

LDI

MAJOR FLT

NO FLT

-

1

0

FAULT

NO FLT

U1-12

(Bit 7)

20

LAO

OVRD TIME

1

h

1

0

-

-

-

21

LDI

FWD.REV

FWD

-

1

0

REV

FWD

U1-12

(Bit 2)

22

LDO

CMD REV.STOP

STOP

-

1

0

REV

STOP

-

23

LDI

RUN.STOP

STOP

-

1

0

RUN

STOP

U1-12

(Bit 0)

24

LDO

CMD RUN.STOP

STOP

-

1

0

FWD

STOP

-

10 APOGEE FLN P1 Communications

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual