Object

ID

Object Name

Units

Default Value

Yaskawa Drive

Parameter

AO 13

Motor Rated Current

A

Motor model dependent

E2-01

AO 14

Jump Frequency 1

0.1 Hz

0.0

d3-01

AO 15

Jump Frequency 2

0.1 Hz

0.0

d3-02

AO 16

Jump Frequency 3

0.1 Hz

0.0

d3-03

AO 17

Jump Frequency Bandwidth

0.1 Hz

1.0

d3-04

AO 18

Number of Auto Restarts

-

0

L5-01

AO 19

Operator Display Mode

-

0

o1-03

AO 20

Power Loss Ride-Thru

seconds

Drive model dependent

L2-02

AO 21

Cable Loss Timeout

seconds

2.0

F6-77

AO 22

Cable Loss Speed

0.01 Hz

0.00

d1-04

AO 23

PI Integral Limit

0.1%

100.0

b5-04

AO 24

PI Upper Limit Value

0.1

100.0

b5-06

AO 25

PI Offset Adjustment

0.1

0.0

b5-07

AO 26

PI Primary Delay Time

0.01

0.00

b5-08

AO 27

PI Feedback Reference Missing

Detection Select

1

0

b5-12

AO 28

PI Feedback Reference Missing

Detection Level

1%

0

b5-13

AO 29

PI Feedback Reference Missing

Detection Time

0.1 s

1.0

b5-14

AO 30

Read Parameter Number

-

-

-

AO 31

Write Parameter Number

-

-

-

AO 32

Write Parameter Data

-

-

-

n

Metasys N2 Binary Input (BI) Summary

Table 12 Metasys N2 Binary Input Summary (SI-J3 to Metasys N2)

Object

ID

Object Name

Default

Off (0) State

On (1) State

BI 1

Run/Stop Monitor

0

Stopped

Running

BI 2

Forward/Reverse Monitor

0

Forward

Reverse

BI 3

Drive Ready Monitor

0

Not Ready

Ready

BI 4

Fault Monitor

0

Not Faulted

Faulted

BI 5

Zero Speed

0

Not Zero Speed

Zero Speed

BI 6

Speed Agree

0

Not Speed Agree

Speed Agree

BI 7

Minor Fault

0

No Minor Fault

Minor Fault

BI 8

Major Fault

0

No Major Fault

Major Fault

BI 9

Drive Communication Error

Monitor

0

No Error

Error

9 Metasys N2 Communications