12

Option Error Codes

u

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive

digital operator as shown in

Table 17

.

Table 17 Option Fault Monitor Descriptions

Fault Condition

Fault

Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults.

Force Fault

EF0

3

Network sent a message to force this node to the fault state.

Communication Loss

Fault

BUS Error

1401

Network communication was established and is now lost.

Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared

upon drive power-up.

• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset

and upon power-up.

Parameter U6-98 retains the original fault value and U6-99 stores the new fault status value

if another fault occurs while the original fault is still active.