Reading and Resetting Faults

The Fault Monitor (BI 4) and Drive Ready Monitor (BI 3) show the current status of the drive.

The Fault Code (AI 10) contains the code for the most current fault. The LST Fault Code (AI

19) contains the code for the previous fault.

Refer to Drive Fault Trace Register Contents

on page 51

for the purpose of interpreting fault codes. The drive faults can be reset through

the Fault Reset Command (BO 4). The Fault Reset Command is only available when the Run

Forward Command and the Run Reverse Command are both OFF.
Set a timer in the master to check how long it takes for the slave drive(s) to respond to the

master. The master should try resending the message if no response is received within a certain

amount of time.

u

Metasys N2 Point Database

This section describes the Metasys N2 point database. This database features logical points:

Analog Inputs (AI), Analog Outputs (AO), Binary Inputs (BI) and Binary Outputs (BO). These

points configure, control, and monitor the operation of the drive.

n

Metasys N2 Analog Input (AI) Summary

Table 10 Metasys N2 Analog Input Summary (SI-J3 to Metasys N2)

Object ID

Object Name

Units

Yaskawa Drive Parameter

AI 1

Speed Reference

0.01 Hz

U1-01

AI 2

Output Sped

0.01 Hz

U1-02

AI 3

Output Current

0.1 A

U1-03

AI 4

kWatt Hour Meter

kWh

U4-10

AI 5

Output Power

0.1 kWh

U1-08

AI 6

Drive Temperature

1 °C

U4-08

AI 7

PI Feedback

0.01%

U5-01

AI 8

AC Output Voltage

0.1 Vac

U1-06

AI 9

DC Bus Voltage

1 Vdc

U1-07

AI 10

Fault Code

-

U2-01

AI 11

Elapsed Time - Hours

1 hour

U4-01

AI 12

Elapsed Time - 10K Hours

10K hours

U4-01

AI 13

MWatt Hour meter

MWh

U4-11

AI 14

Drive Rated Current

A

n9-01

AI 15

Communication Error Code

-

-

AI 16

PI Deviation

0.01%

U5-02

AI 17

PI Output Capacity

0.01%

U5-03

AI 18

PI Reference

0.01%

U5-04

AI 19

Last Fault Code

-

U2-02

9 Metasys N2 Communications

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual