Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Parameter

85

LAO

PID FB RMDL

0

%

1

0

-

-

b5-13

86

LAO

PID FB RMDT

1

s

0.1

0

-

-

b5-14

87

LAI

PID OUT CAP

0

%

0.01

0

-

-

U5–03

88

LAI

PID REF

0

%

0.01

0

-

-

U5-04

89

LAI

COMM ERR CD

0

-

1

0

-

-

U1-19

90

LDO

COMM FLT ENA

ENABLE

-

1

0

ENABLE

DISABLE

F6–76

91

LAO

CBL LOSS FRQ

0

Hz

0.01

0

-

-

d1-04

92

LAO

CBL LOSS TMR

2

s

0.1

0

-

-

F6–77

93

LDI

OK.FAULT

OK

-

1

0

FAULT

OK

U1-12

(Bit 7)

94

LDO

RESET FAULT

NO

-

1

0

RESET

NO

-

95

LDI

DRV COMM ERR

NO FLT

-

1

0

FAULT

NO FLT

-

96

LDO

EXTERNAL FLT

OK

-

1

0

FAULT

OK

-

97

LDI

MF IN 5 MON

OFF

-

1

0

ON

OFF

U1-10

(Bit 6)

99

LAI

ERROR STATUS

0

-

1

0

-

-

-

<1>

Set H1-03 to 70 , Drive Enable2, for point 35 to work properly.

u

APOGEE FLN P1 Cable Loss Configuration and Behavior

This section describes the configurable cable loss feature of the drive. This feature offers a

user maximum flexibility in determining the drive response to a loss of communication.

n

Drive Behavior At Loss of Communication

The drive can be configured to respond in one of the following manners after some interval

without receipt of a message:
• Continue at last speed
• Continue at last speed with Alarm
• Continue at preset speed
• Ramp to Stop with EF0 fault
• Coast to Stop with EF0 fault
• Emergency Stop with EF0 fault

10 APOGEE FLN P1 Communications