Table 5, Figure 7, 5 installation procedure – Yaskawa APOGEE FLN P1 User Manual

Page 19

Advertising
background image

Table 5 Communication Wire Routing Selection

Drive Series

Model

Wire Routing <1>

Through

Front Cover

Inside Drive

P1000

CIMR-PU2A0004 to 0040;

CIMR-PU4A0002 to 0023;

CIMR-PU5A0003 to 0011

Figure 7

(A)

-

CIMR-PU2A0056 and above;

CIMR-PU4A0031 and above;

CIMR-PU5A0023 and above

-

Figure 7

(B)

iQpump1000

CIMR-PW2A0004 to 0040;

CIMR-PW4A0002 to 0023;

CIMR-PW5A0003 to 0011

Figure 7

(A)

-

CIMR-PW2A0056 and above;

CIMR-PW4A0031 and above;

CIMR-PW5A0023 and above

-

Figure 7

(B)

<1> Refer to

Figure 7

for examples of the different wire routing techniques.

A

B

A – Route wires through the

openings provided on the
left side of the front
cover.

<1>

B – Use the open space

provided inside the drive
to route option wiring.

Figure 7 Wire Routing Examples

<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.

2.

Connect the network communication cables to the option modular connector terminal
block (TB1).

Note:

Separate the communications cables from the main circuit cables and other wiring and power

cables. Use properly grounded shielded cables for the communication cables to prevent

problems caused by electrical interference.

5 Installation Procedure

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual

19