Yaskawa APOGEE FLN P1 User Manual

Page 34

Advertising
background image

n

Continue at Last Speed

Cable Loss Timeout (AO 21) is set to 0, disabling the cable loss feature in this mode. The

other two settings Cable Loss Speed (AO 22) and Communication Fault Enable (BO 11) are

ignored. The drive simply maintains its last commanded state if communication is lost. The

drive will not display an alarm or fault to indicate it has lost communication. This behavior

can also be achieved by setting parameter F6-01 to 3. The drive will display an alarm and

continue running. The Communication Fault Enable (BO 11) must be enabled and Cable Loss

Timeout (AO 21) should be set to a value other than 0 for this specific condition.

n

Continue at Preset Speed

Cable Loss Timeout (AO 21) is set to the desired interval, Cable Loss Speed (AO 22) is set

to the desired preset speed and F6-01 is set to 4 in this mode. The drive speed command (AO

1) is set to the Cable Loss Speed (AO 22) and the drive continues running at this new speed

if the time between messages exceeds the timeout interval. Communication Fault Enable (BO

11) must be set to ON.

n

Stop with Fault (BUS)

Communication Fault Enable (BO 11) must be set to ON. Cable Loss Timeout (AO 21) is set

to the desired interval and parameter F6-01 is set to a value of 0,1 or 2 in this mode. If the

time between messages exceeds the timeout interval, the drive will declare a BUS fault and

the drive speed command (AO 1) will be set to 0. The stopping method is determined by the

setting of F6-01.
• F6-01=0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined

by the setting of drive parameter C1-02.

• F6-0 =1 selects Coast to Stop. The drive does not attempt to control the rate of deceleration.
• F6-0 =2 selects Emergency or Fast Stop. The deceleration time is determined by the setting

of drive parameter C1-09.

Note:

The behavior of the drive at cable loss is controlled by parameter F6-01. This drive parameter works

with the points as described in the table above to determine how the drive will respond to a cable loss.

The drive will continue in its last state if the cable loss fault is disabled. The drive will continue to run

at the last commanded frequency if running.

9 Metasys N2 Communications

34

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual