Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Parameter

25

LDI

ZERO SPEED

OFF

-

1

0

ON

OFF

U1-12

(Bit 1)

26

LDI

SPEED AGREE

NO AGR

-

1

0

AGREE

NO AGR

U1-12

(Bit 4)

27

LDI

DRIVE READY

NOTRDY

-

1

0

READY

NOTRDY

U1-12

(Bit 5)

28

LDI

LOC.REM MON

REMOTE

-

1

0

LOCAL

REMOTE

-

29

LDO

DAY.NGT

DAY

-

1

0

NGT

DAY

-

30

LAO

CURRENT LMT

0

A

0.01

0

-

-

E2-01

31

LAO

ACCEL TIME

0

s

0.1

0

-

-

C1-01

32

LAO

DECEL TIME

0

s

0.1

0

-

-

C1-02

33

LDO

LOCK PANEL

UNLOCK

-

1

0

LOCK

UNLOCK

-

35

<1>

LDO

RUN ENABLE

STOP

-

1

0

ENABLE

STOP

-

36

LAO

STALL PRE RN

90

%

1

30

-

-

L3-06

37

LAO

STALL PRE AC

120

%

1

0

-

-

L3-02

38

LAO

FREQ UP LIM

100

%

0.1

0

-

-

d2-01

39

LAO

FREQ LOW LIM

0

%

0.1

0

-

-

d2-02

40

LDI

MULTI OUT 1

OFF

-

1

0

ON

OFF

U1-11

(Bit 0)

41

LDI

MULTI OUT 2

OFF

-

1

0

ON

OFF

U1-11

(Bit 1)

42

LDI

MULTI OUT 3

OFF

-

1

0

ON

OFF

U1-11

(Bit 2)

43

LDI

SAFETY ILOCK

OFF

-

1

0

ON

OFF

U1-10

(Bit 2)

44

LDO

MF INP 1

OFF

-

1

0

ON

OFF

-

45

LDO

MF INP 2

OFF

-

1

0

ON

OFF

-

46

LDO

MF INP 3

OFF

-

1

0

ON

OFF

-

47

LDO

MF INP 4

OFF

-

1

0

ON

OFF

-

48

LDO

MF INP 5

OFF

-

1

0

ON

OFF

-

49

LAO

JUMP FREQ 1

0

Hz

0.1

0

-

-

d3-01

50

LAO

JUMP FREQ 2

0

Hz

0.1

0

-

-

d3-02

51

LAO

JUMP FREQ 3

0

Hz

0.1

0

-

-

d3-03

52

LAO

JUMP FREQ BW

0

Hz

0.1

0

-

-

d3-04

53

LAO

NUM AUTOSTRT

0

-

1

0

-

-

L5-01

10 APOGEE FLN P1 Communications