13

Option Compatibility

A limited number of options may be simultaneously connected to the drive depending on the

type of option. Refer to

Table 18

for more information. More details can be found in the

Options and Peripheral Devices chapter of the drive Technical Manual.

Table 18 Option Installation Compatibility

OptionConnector

Connector

Number of Possible Options

SI-C3, SI-J3, SI-N3, SI-P3, SI-S3, SI-EN3
etc.

<1>

CN5-A

1

PG-B3, PG-X3 etc.

CN5-B, C

2

<1>

DO-A3, AO-A3, AI-A3, DI-A3 etc.

CN5-A, B, C

1

<1>

The AI-A3 and DI-A3 options can be used to set the frequency reference or replace the drive analog inputs with
higher resolution when installed in CN5-A. These options can only be used for monitoring when installed in
CN5-B or CN5-C,; their input levels will be displayed in U1-17 or U1-21 to U1-23.

n

Drive Fault Trace Register Contents

Table 19 Drive Fault Trace Register Contents

Fault

Code

Fault Name

0002H

Undervoltage (Uv1)

0003H

Control Power Supply Undervoltage (Uv2)

0004H

Soft Charge Circuit Fault (Uv3)

0006H

Ground Fault (GF)

0007H

Overcurrent (oC)

0008H

Overvoltage (ov)

0009H

Heatsink Overheat (oH)

000AH

Heatsink Overheat (oH1)

000BH

Motor Overload (oL1)

000CH

Drive Overload (oL2)

000DH

Overtorque Detection 1 (oL3)

0010H

Braking Resistor Overheat (rH)

0011H

External Fault at Input Terminal S3 (EF3)

0012H

External Fault at Input Terminal S4 (EF4)

0013H

External Fault at Input Terminal S5 (EF5)

0014H

External Fault at Input Terminal S6 (EF6)

0015H

External Fault at Input Terminal S7 (EF7)

001BH

Input Phase Loss (PF)

001CH

Output Phase Loss (LF)

Fault

Code

Fault Name

001DH

Motor Overheat (PTC input) (oH3)

001EH

Digital Operator Connection (oPr)

001FH

EEPROM Write Error (Err)

0020H

Motor Overheat (PTC input) (oH4)

0021H

MEMOBUS/Modbus Communication Error

(CE)

0022H

Option Communication Error (bUS)

0027H

Option External Fault (EF0)

0028H

PI Feedback Loss (FbL)

0029H

Undertorque Detection 1 (UL3)

002BH

High Slip Braking Overload (oL7)

0030H

Hardware Fault (including oFx)

0036H

Output Current Imbalance (LF2)

0037H

Pullout Detection (Sto)

003BH

Too Many Speed Search Restarts (SEr)

0041H

PI Feedback Loss (FbH)

0042H

External Fault 1, Input Terminal S1 (EF1)

0043H

External Fault 2, Input Terminal S2 (EF2)

0046H

Current Offset Fault (CoF)

0047H

PLC Detection Error 1 (PE1)

13 Option Compatibility