4 option components – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 13

Advertising
background image

The operational states of the option LEDs after completion of the BACnet power-up diagnostic

LED sequence are described in

Table 3

. Wait at least 2 seconds for the power-up diagnostic

process to complete before verifying LED states.

Table 3 Option LED States

Name

Display

Operating Status

Remarks

Color

Status

MS

OFF

Power supply OFF

Power is not being supplied to the drive.

Green

ON

Normal operation

The option is operating normally and

initialization is complete.

Green

Flashing

Standby/Initializing

The option is in process of configuring or

waiting for configuration information.

Red

Flashing

Minor fault

The option has detected a recoverable

minor fault such as incomplete

configuration.

Red

ON

Major fault

The option has detected an unrecoverable

major fault.

Green/Red

Flashing

Option self-test

The option is in self-test mode.

NS

OFF

Power supply OFF

Green

ON

Connected

The device is currently communicating on

the network.

Green

Flashing

Not connected

The device currently is not communicating,

but is correctly configured. The state is

“waiting” for communication to resume.

Red

Flashing

Minor fault

A minor recoverable fault has occurred.

Red

ON

Major fault

A non-recoverable major network fault has

occurred.

Green/Red

Flashing

Network test

Power-up sequence and testing

TX

OFF

No data being sent to the

network

This node is not sending any data.

Green

Flashing

Data being sent to the

network

This node is sending network data.

RX

OFF

No data seen on the

network

The option is not physically connected to

the network or there is no network activity.

Green

Flashing

Data is seen on the

network

The option is connected to a network.

4 Option Components

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual

13