Analog output objects, Analog value objects, 9 bacnet objects supported – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 38

Advertising
background image

u

Analog Output Objects

Table 13 Analog Output Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AO1

Analog Output 1 Level

0007H

XXXX.X

0 to 100.0

%

C

AO2

Not Used AO2

0008H

XXXX.X

0 to 100.0

%

C

u

Analog Value Objects

Table 14 Analog Value Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AV1

Operation Cmd

0001H

XXXXX

0 to 65535

C

AV2

Frequency Cmd

0002H

XXX.XX

Depends on

o1-03

0.00 to

600.00

Hz

Depends on

o1-03

C

AV3

PI Setpoint Cmd

0006H

XXX.XX

0.00 to

100.00

%

C

AV4

MF Output 1 Cmd

0009H

XXXXX

0 to 255

C

AV5

Reference Select Cmd

000FH

XXXXX

C

AV6

Drive Status

0020H

XXXXX

R

AV7

Fault Details

0021H

XXXXX

R

AV8

Data Link Status

0022H

XXXXX

R

AV9

Frequency Reference

0040H

XXX.XX

Depends on

o1-03

Hz

Depends on

o1-03

R

AV10

Output Frequency

0041H

XXX.XX

Depends on

o1-03

Hz

Depends on

o1-03

R

AV11

Output Voltage

0045H

XXXX.X

Volts

R

AV12

Output Current

0026H

XXXX.X

Amps

R

AV13

Output Power

0047H

XXXX.X

(for drives

rated above

11 kVA)

XXX.XX

(for drives

rated 11

kVA or

lower)

kW

R

AV14

Torque Reference

0048H

XXXX.X

%

R

AV15

MF Input Status

002BH

XXXXX

R

9 BACnet Objects Supported

38

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual