Communication errors, Bus fault tolerance – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 34

Advertising
background image

n

Communication Errors

Errors that may occur when accessing drive parameters using the BACnet objects are shown

in

Table 8

.

Table 8 MEMOBUS to BACnet Error Conversion

Error Code

Description

03d

BN_ERR_DEVICE_IS_BUSY

Writing to a parameter was attempted while the drive was saving parameters to non-volatile

memory.

27d

BN_ERR_READ_ACCESS_DENIED

Invalid parameter register number used when reading.

37d

BN_ERR_VALUE_OUT_OF_RANGE

Value written to the parameter is out of the valid range.

40d

BN_ERR_WRITE_ACCESS_DENIED

An invalid parameter register number was used when writing.

Writing to a parameter was attempted while the drive was in a mode that disables writing (i.e.,

writing while the drive was Auto-Tuning).

Writing to a parameter was attempted while the DC Bus had an Undervoltage (Uv) fault.

n

bUS Fault Tolerance

bUS Fault Auto-Restart

Parameter F6-14, bUS Fault Auto Reset Select, will appear when the option is installed.
Setting F6-14 = 0 (Disabled) or F6-01 = 3 or greater (Alarm only) will cause the drive to

declare an alarm after the time set in F6-04 has passed.
Setting F6-14 = 1 (Enabled) AND F6-01

≠ 3 (Fault) will cause the following operation: The

bUS fault occurs after the F7-16 + F6-04 delay time and the Run command is removed from

the drive. Then the option throws a bUS fault to the drive. When the condition is removed,

the option commands a fault reset and returns control of the drive to the BACnet network.

Note:

The option will only read parameters F6-01 and F6-14 from the drive during power-up.

bUS Fault Delay

Parameter F7-16, Communications Loss Detection Time Delay, will appear when the option

is installed.
The setting value of F7-16 + F6-04 is the length of time that the option will delay sending the

bUS fault to the drive.
The status LEDs on the option are not affected by the delay time set in F7-16; the LEDs will

indicate the bUS condition immediately.

Note:

The option will only read parameters F6-04 and F7-16 from the drive during power-up.

7 Troubleshooting

34

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual