Drive Operations by BACnet

The drive operations that can be performed by BACnet communication depend on drive

parameter settings. This section explains the functions that can be used and related parameter

settings.

u

Observing the Drive Operation

A controller can perform the following actions with BACnet communications at any time

regardless of parameter settings:
• observe drive status and drive control terminal status from a controller
• read and write parameters
• set and reset faults
• set multi-function inputs.

Note:

Input settings from the input terminals So and from BACnet communications are both linked by a logical

OR operation.

u

Controlling the Drive

Select an external reference and adjust the parameters in

Table 9

accordingly to start and stop

the drive or set the frequency reference using BACnet communications.

Table 9 Setting Parameters for Drive Control from BACnet

Reference Source

Parameter

Name

Required Setting

External Reference 1

b1-01

Frequency Reference Selection 1

3

b1-02

Run Command Selection 1

3

External Reference 2

b1-15

Frequency Reference Selection 2

3

b1-16

Run Command Selection 2

3

8 Drive Operations by BACnet

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual