Minor faults and alarms, 7 troubleshooting – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 33

Advertising
background image

n

Minor Faults and Alarms

Digital Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solutions

Minor Fault

(H2-oo = 10)

Communications wiring is faulty,

there is a short circuit, the wiring

is incorrect, or the connections are

poor.

• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as

needed.

YES

Programming error on the master

side.

Check communications at start-up and correct programming

errors.

Communications circuitry is

damaged.

• Perform a self-diagnostics check.
• If the problem continues, replace the control board or the

entire drive. Contact Yaskawa for instructions on replacing

the control board.

7 Troubleshooting

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual

33