Digital Operator Display

Fault Name

EF0

Option Card External Fault
The alarm function for an external device has been triggered.

Cause

Possible Solutions

An external fault was received from

the PLC and F6-03 is set to a value

other than 3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

Digital Operator Display

Fault Name

oFA00

Option Card Connection Error at Option Port CN5.
The option card is incompatible with the drive.

Cause

Possible Solution

Digital Operator Display

Fault Name

oFA01

Option Card Fault
Option not properly connected

Cause

Possible Solution

The option card connection is

faulty

• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure

the card is fixed properly.

Digital Operator Display

Fault Name

oFA03

Option Card Fault
Option card self-diagnostic error

oFA04

Option Card Fault
An error occurred attempting to write to the option card memory.

to

oFA30 to

oFA43

Option Card Fault

Communication ID error

Cause

Possible Solution

Option card or hardware is

damaged.

Replace the option card. Contact Yaskawa for consultation.

7 Troubleshooting

32

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual