Related Drive Parameters

The following parameters are used to set up the drive for operation with the option. Parameter

setting instructions can be found in the drive Quick Start Guide or Technical Manual.
Confirm proper setting of the all parameters in

Table 7

before starting network

communications. After changing parameter settings, cycle power to the drive for the new

settings to take effect.

Table 7 Related Parameters

No.

(Addr.

Hex)

Name

Description

Values

b1-01

(0180)

<1>

Frequency Reference

Selection

Selects the frequency reference input source.

0: Operator - Digital preset speed d1-01 to d1-17

1: Terminals - Analog input terminal A1 or A2

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse Input (Terminal RP)

Default: 1

Range: 0 to 4

(Set to 3 for BACnet)

b1-02

(0181)

Run Command

Selection

Selects the run command input source.

0: Digital Operator - RUN and STOP keys

1: Digital input terminals S1 to S7

2: MEMOBUS/Modbus communications

3: Option PCB

Default: 1

Range: 0 to 3

(Set to 3 for BACnet)

F6-01

(03A2)

Communications

Error Operation

Selection

0: Ramp to stop. Decelerate to stop using the deceleration time

in C1-02.

1: Coast to stop

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09.
3: Alarm only

<2>

Default: 1

Range: 0 to 3

F6-02

(03A3)

External Fault from

Comm. Option

Detection Selection

1: Detection during run only

Default: 0

Range: 0, 1

F6-03

(03A4)

External Fault from

Comm. Option

Operation Selection

0: Ramp to stop. Decelerate to stop using the deceleration time

in C1-02.

1: Coast to stop

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09.
3: Alarm only

<2>

Default: 1

Range: 0 to 3

F6-04

(03A5)

bUS Error Detection

Time

Sets the delay time for error detection if a bUS error occurs.

Default: 2.0 s

Min.: 0.0

Max.: 5.0

F6-07

(03A8)

Multi-Step Speed

Enable/Disable

Selection when

NefRef/ComRef is

Selected

0: Multi-step reference disabled (same as F7)

1: Multi-step reference enabled (same as V7)

Default: 1

Range: 0, 1

6 Related Drive Parameters