9 bacnet objects supported – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 39

Advertising
background image

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AV16

Drive Status 2

002CH

XXXXX

R

AV17

MF Output Status

002DH

XXXXX

R

AV18

DC Bus Voltage

0031H

XXXX.X

Volts

R

AV19

PI Feedback Level

0038H

XXXX.X

%

R

AV20

PI Input Level

0039H

XXXX.X

%

R

AV21

PI Output Level

003AH

XXXX.X

%

R

AV22

CPU Software

004DH

XXXXX

R

AV23

Flash Number

005BH

XXXXX

R

AV24

Comm Error Detail

003DH

XXXXX

R

AV25

kVA Setting

0508H

XXXXX

R

AV26

Control Method

0102H

XXXXX

R

AV27

Accel Time

0200H

XXXX.X

(when

C1-10 = 1)

XXX.XX

(when

C1-10 = 0)

0.0 to 6000.0

(when

C1-10 = 1)

0.00 to

600.00

(when

C1-10 = 0)

Sec

W

AV28

Decel Time

0201H

XXXX.X

(when

C1-10 = 1)

XXX.XX

(when

C1-10 = 0)

0.0 to 6000.0

(when

C1-10 = 1)

0.00 to

600.00

(when

C1-10 = 0)

Sec

W

AV29

<1>

Parameter Number

XXXXX

0 to FFFFH

W

AV30

<1>

Parameter Data

XXXXX

0 to FFFFH

W

AV31

Not Used

AV32

Not Used

AV33

Drive kWH

0x005C and

0x005D

XXXXXXX

.X

0.0 to

32767999.9

kWH

R

AV34

Not Used

<1>

Refer to Accessing Drive Parameters and the Enter Command on page 43

for an explanation of how to read

and write drive parameters not listed in the analog or binary objects.

9 BACnet Objects Supported

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual

39