Analog input objects, 9 bacnet objects supported – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 37

Advertising
background image

Property

Object Type

Device

Analog

Input

Analog

Output

Analog

Value

Binary

Input

Binary

Output

Binary

Value

ADPU_Timeout

Yes

Number_Of_ADPU_Retries

Yes

Max_Masters

Yes

Max_Info_Frames

Yes

Device_Address_Binding

Yes

Database_Revision

Yes

Present_Value

Yes

Yes

Yes

Yes

Yes

Yes

Status_Flags

Yes

Yes

Yes

Yes

Yes

Yes

Event_State

Yes

Yes

Yes

Yes

Yes

Yes

Reliability

Yes

Yes

Yes

Yes

Yes

Yes

Out_Of_Service

Yes

Yes

Yes

Yes

Yes

Yes

Units

Yes

Yes

Yes

Priority_Array

Yes

<1>

Yes

<1>

Yes

Yes

Relinquish_Default

Yes

<1>

Yes

<1>

Yes

Yes

Polarity

Yes

Yes

Inactive_Text

Yes

Yes

Yes

Active_Text

Yes

Yes

Yes

<1>

For Commandable Object Instances only.

u

Analog Input Objects

Table 12 Analog Input Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AI1

Analog Input 1 Level

004EH

XXXX.X

%

R

AI2

Analog Input 2 Level

004FH

XXXX.X

%

R

AI3

Not Used AI3

AI4

Not Used AI4

AI5

Not Used AI5

AI6

Display Format o1-03

0502H

XXXXX

R

AI7

Scale Format b5-20

01E2H

XXXXX

R

AI8

Inverter Model o2-04

0508F

XXXXX

R

AI9

Rated Current n9-01

05D0H

XXXX.X

Amps

R

9 BACnet Objects Supported

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual

37