9 bacnet objects supported – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 41

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive

Text

PV Access

BV6

Com Cntrl Cmd

0001H:bit 5

COM

LOCAL

C

BV7

MF Input 3 Cmd

0001H:bit 6

ON

OFF

C

BV8

MF Input 4 Cmd

0001H:bit 7

ON

OFF

C

BV9

MF Input 5 Cmd

0001H:bit 8

ON

OFF

C

BV10

MF Input 6 Cmd

0001H:bit 9

ON

OFF

C

BV11

MF Input 7 Cmd

0001H:bit 10

ON

OFF

C

BV12

Set Fault Contact Cmd

0009H:bit 6

ENABLE

OFF

C

BV13

RUN-STOP

0020H:bit 0

RUN

OFF

R

BV14

REV-FWD

0020H:bit 1

REV

FWD

R

BV15

READY

0020H:bit 2

READY

OFF

R

BV16

FAULT

0020H:bit 3

FAULTED

OFF

R

BV17

Data Set Error

0020H:bit 4

ERROR

OFF

R

BV18

Overcurrent – Gnd Fault

0021H:bit 0

OC-GF

OFF

R

BV19

Main Ckt Overvoltage

0021H:bit 1

OV

OFF

R

BV20

Drive Overload

0021H:bit 2

OL2

OFF

R

BV21

Drive Overheat

0021H:bit 3

OH1-OH2

OFF

R

BV22

Fuse Blown

0021H:bit 5

PUF

OFF

R

BV23

PI Feedback Loss

0021H:bit 6

FBL

OFF

R

BV24

External Fault

0021H:bit 7

EF0-EF

OFF

R

BV25

Hardware Error

0021H:bit 8

CPF

OFF

R

BV26

Mtr Ovrld-OvrTorque

0021H:bit 9

OL1-OL3

OFF

R

BV27

Overspeed

0021H:bit 10

OS-DEV

OFF

R

BV28

Main Ckt Undervoltage

0021H:bit 11

UV

OFF

R

BV29

MCU, Cntl Pwr Sy Err

0021H:bit 12

UV1-2-3

OFF

R

BV30

Output Phase Loss

0021H:bit 13

LF

OFF

R

BV31

Communication Error

0021H:bit 14

CE

OFF

R

BV32

Operator Disconnect

0021H:bit 15

OPR

OFF

R

BV33

Operating

002CH:bit 0

OPERATING

OFF

R

BV34

Zero Speed

002CH:bit 1

ON

OFF

R

BV35

Frequency Agree

002CH:bit 2

ON

OFF

R

BV36

Desired Freq Agree

002CH:bit 3

ON

OFF

R

BV37

Frequency Detect 1

002CH:bit 4

ON

OFF

R

BV38

Frequency Detect 2

002CH:bit 5

ON

OFF

R

BV39

Drv Startup Complete

002CH:bit 6

ON

OFF

R

9 BACnet Objects Supported

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual