6 related drive parameters – Yaskawa BACnet MS/TP SI-B3/V User Manual

Page 30

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

F6-08

(036A)

<3>

Reset

Communication

Parameters

0: Communication-related parameters (F6-oo/F7-oo) are

not reset when the drive is initialized using A1-03.

1: Reset all communication-related parameters

(F6-oo/F7-oo) when the drive is initialized using A1-03.

Default: 0

Range: 0, 1

F6-14

(03BB) bUS Error Auto Reset

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

F6-45

(02FB) Drive Node Address

Sets the BACnet MS/TP MAC address (physical node

address).

Default: 1

Range: 0 to 127

F6-46

(02FC)

Communication

Speed Selection

Sets the communication speed.

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Default: 3

Range: 0 to 8

F6-47

(02FD)

Drive Transmit Wait

Time

Sets the time the drive waits after receiving data from a master

before transmitting response data.

Default: 5 ms

Range: 5 to 65

F6-48

(02FE)

<2>

BACnet Device

Object Identifier 0

Set the Instance Identifier of the BACnet Device Object,

where the F6-48 value is the least significant word.

Default: 1

Range: 0 to FFFFH

F6-49

(02FF)

<2>

BACnet Device

Object Identifier 1

Set the Instance Identifier of the BACnet Device Object,

where the F6-49 value is the most significant word.

Default: 0

Range: 0 to 3FH

F7-16

(03F4)

Communication Loss

Timeout

Sets the timeout value for communication loss detection in

tenths of a second.

Example: An entered value of 100 represents 10.0 seconds.

Default: 0.0

Min.: 0.0

Max.: 30.0

<1>

To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control
the drive frequency reference via the master device, set b1-01 to 3.

<2>

These parameters set the Instance Identifier of the BACnet Device Object, where the F6-48 value is the least
significant word and the F6-49 value is the most significant word.
Example 1: Set the Device Object Instance Identifier of "1234". 1234 decimal is equal to 4D2H (hexadecimal).
Set F6-48 to 4D2H and F6-49 to 0.
Example 2: Set Device Object Instance Identifier to "1234567". 1234567 decimal is equal to 12D687H. Set
F6-48 to D687H and set F6-49 to 12H.

<3>

Parameter setting value is not reset to the default value when the drive is initialized.

6 Related Drive Parameters

30

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual