Enter Command

Enter Commands are only required when using AV29 and AV30 to write drive parameters.

An Enter command is not required when reading or writing to the other BACnet objects.
When writing parameters to the drive from a controller using BACnet communications, an

Enter command must be issued to enable these parameters. This section describes the types

and functions of the Enter commands.

n

Enter Command Types

The drive supports two types of Enter commands as shown in

Table 18

.

Table 18 Enter Command Types

BACnet Object

Modbus Address

Description

BV55 (Write “ON”)

0910H (bit 0)

Writes data in the active RAM only. Parameter changes are lost

when the drive is shut off.

BV56 (Write “ON”)

0900H (bit 0)

Simultaneously writes data into the EEPROM (non-volatile

memory) of the drive and enables the data in active RAM.

Parameter changes remain after cycling power.

Note:

The EEPROM can only be written to 100,000 times, so it is recommended to limit the number of times

writing to the EEPROM. The Enter command registers 0900H and 0910H are write-only and if these

registers are read, the register address will be invalid. However, BACnet objects BV55 and BV56 can

be read without error.

10 Accessing Drive Parameters and the Enter Command

44

YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual