2 installation, 1 checking installation site, Installation site – Yaskawa Varispeed-656 DC5 User Manual

Page 15: Caution, 2installation

Advertising
background image

2 INSTALLATION

E-5

2

INSTALLATION

This chapter describes the configuration, location, and space when mounting the VS-656DC5.

2.1

Checking Installation Site

„

Installation Site

Install the VS-656DC5 under the following conditions.

To ensure proper performance and long operating life, follow the recommendations below
when choosing a location for installing the VS-656DC5. Make sure the VS-656DC5 is pro-
tected from the following conditions:

• Extreme cold and heat

Use only within ambient temperature range: -10

°C to +45 °C

• Rain, moisture
• Oil sprays, splashes
• Salt spray
• Direct sunlight (Avoid using outdoors.)
• Corrosive gases or liquids
• Dust or metallic particles in the air
• Physical shock, vibration
• Magnetic noise (Example: welding machines, power devices, etc.)
• High humidity
• Radioactive materials
• Combustibles: thinners, solvents, etc.

• Lift the cabinet by the base. When moving the VS-656DC5, never lift by the front cover or the front

panel.

Otherwise, the main unit may be dropped causing personal injury or damage to the VS-656DC5.

• Mount the VS-656DC5 on nonflammable material (i.e. metal).

Failure to observe this caution may result in a fire.

• When mounting several Units in an enclosure, install a fan or other cooling device to keep the

intake air temperature below 45

°C.

Overheating may cause a fire or damage to the VS-656DC5.

CAUTION

Type

Ambient Operating Temperature

Humidity

Open chassis

-10 to + 45

°C

90 % RH or less (no condensation)

Advertising