A.3 multi-function i/o terminals (h constants) – Yaskawa Varispeed-656 DC5 User Manual
Page 67

Appendix A CONSTANTS LIST
E-57
A.3
Multi-function I/O Terminals (H Constants)
Table 14 Multi-function Input Functions
Setting Value
Function
(H1-01, 02, 03, 04, 05, 06)
Remarks
08
External Baseblock (NO Contact)
[Ext BaseBlk N.O.]
09
External Baseblock (NC Contact)
[Ext BaseBlk N.C.]
0F
Not Used
[Term Not Used]
14
Fault Reset
[Fault Reset]
24-27
External fault
[External Fault]
2C-2F
Table 15 Multi-function Output Functions
Setting Value
Function
(H2-01, 02, 03)
Remarks
00
During Run
[During Run]
01
Inverter Ready
[Inverter Ready]
06
Converter Unit Ready
[Converter Ready]
07
During DC Bus Undervoltage (UV)
Detection
[DC Bus Undervolt]
08
During Baseblock
[BaseBlock]
0A
During MCON
[MCON]
0E
Fault
[Fault]
0F
Not used
[Not Used]
10
Alarm
[Minor Fault]
11
Fault Reset Command Active
[Reset Cmd Active]
1D
Motoring/regenerating
[Regenerating]
1E
Restart Enabled
[Restart Enabled]
1F
Overload (OL1) Pre-alarm
[Overload (OL1)]
20
Overheat pre-alarm
[OH Prealarm]