Yaskawa Varispeed-656 DC5 User Manual
Page 36

E-26
* Wire size is determined by 75
°C temperature-rated copper wire, and assuming external wiring
of single 3-core wires at an ambient temperature of 30
°C.
D5A4030
R/L1, S/L2, T/L3,
, , ,
M8
8.2 to 10.2
14 to 70
(6 to 2/0)
22
(4)
Power cable:
600 V vinyl
sheathed wire or
equivalent
r1/
11,
1/
21, t1/
31
M4
1.2 to 1.4
2 to 5.5
(14 to 10)
−
M6
4.0 to 5.0
8 to 14
(8 to 6)
8
(8)
D5A4045
R/L1, S/L2, T/L3,
, , ,
M8
8.2 to 10.2
30 to 70
(2 to 2/0)
38
(1)
r1/
11,
1/
21, t1/
31
M4
1.2 to 1.4
2 to 5.5
(14 to 10)
−
M6
4.0 to 5.0
14
(6)
14
(6)
D5A4075
R/L1, S/L2, T/L3
M10
18 to 23
50 to 100
(1/0 to 4/0)
80
(3/0)
, , ,
M10
18 to 23
50 to 70x2P
(1/0 to 2/0x2P)
30x2P
(2x2P)
M8
9.0 to 11.0
22
(4)
22
(4)
r1/
11,
1/
21, t1/
31
M4
1.2 to 1.4
2.0 to 5.5
(14 to 10)
−
D5A4160
R/L1, S/L2, T/L3
M12
31.5 to 39.5
150 to 200
(300 to 400)
200
(400)
, , ,
M12
31.5 to 39.5
38x2P to
100x2P
(1x2P to
4/0x2P)
70x2P
(2/0x2P)
M8
9.0 to 11.0
50
(1/0)
50
(1/0)
r1/
11,
1/
21, t1/
31
M4
1.2 to 1.4
2.0 to 5.5
(14 to 10)
−
Table 4 400 V Class Wire Size (cont’d)
Inverter
Model
CIMR-
Terminal Symbol
Terminal
Screw
Tightening
Torque
Nxm
Possible
Wire Size
*
mm
2
(AWG)
Recom-
mended Wire
Size
mm
2
(AWG)
Wire Type