7 specifications, 7specifications – Yaskawa Varispeed-656 DC5 User Manual

Page 58

Advertising
background image

E-48

7

SPECIFICATIONS

* Contact your YASKAWA representative. (Under development)

Voltage Class

200 V Class

400 V Class

Model CIMR-D5A†

2015 2022

2037 2055

* 2075 4015

4022 4030 4045 4075 4160 4300

*

Rating

Rated Capacity kW

20

30

50

75

90

20

30

40

60

100

185

370

Rated Output Current (DC) A

60

90

150

210

280

30

45

60

90

150

280

560

Rated Input Current (AC) A

64

96

160

224

300

32

48

64

96

165

300

600

Rated Output Voltage

330 VDC

660 VDC

In

put Po

wer

Suppl

y Voltage Frequency

200 to 220 VAC 50 Hz,

200 to 230VAC 60 Hz

380 to 460VAC 50/60Hz

Allowable Voltage Fluctuation

+10% to -15%

Allowable Frequency
Fluctuation

±3 Hz/300 ms (Free phase rotation)

Control Cha

racte

risti

cs Control Method

Sine wave PWM method

Input Power Factor

0.95 or more (Rated current)

Output Voltage Accuracy

±5%

Overload Capacity

Stops in 1 minute at approx. 150% of rated current.

Operation Input

Digital Operator and external terminals

S

tatu

s Output

Fault

1NONC contact output

Running

1NO contact output

Minor Fault, etc.

Multi-function PHC output: 2 points can be selected.

Analog Output

Multi-function analog output: 2 points can be selected.

Constant Setting

Using the Digital Operator

Protective Fu

ncti

on

Instantaneous Overcurrent

Stops at approx. 200% of the VS-656DC5 input current.

Blown Fuse

Motor stops by blown fuse.

Overload

Stops after 1 minute at 150% of rated current (power running and regenerating).

Undervoltage (Output)

Stops at approx. 190 VDC or less

Stops at approx. 380 VDC or less.

Undervoltage (Input)

Stops at approx. 150 VAC or less.

Stops at approx. 300 VAC or less.

Overvoltage

Stops at approx. 400 VDC or more.

Stops at approx. 800 VDC or more.

Fin Overheat

Protected by thermistor

Ground Fault Detection

Protected by electronic circuit

Power Frequency Error

Stops by fluctuation more than

±3 Hz of rated input frequency.

Power Charge Indication

Indicated until main circuit output voltage is approx. 50 V or less.

En

vironmen

ta

l C

ondi

tions

Location

Indoor (Protected from corrosive gases and dust)

Ambient Temperature

-10

°C to +45 °C

Humidity

90% RH or less (non-condensing)

Vibration

9.8 m/s

2

(1 G) less than 20 Hz, up to 1.96 m/s

2

(0.2 G) at 20 to 50 Hz

Advertising