Appendix A CONSTANTS LIST

E-55

H1-04

Multi-function Input (Terminal 6)

[Terminal 6 Sel]

0F

00 to FF

Possible

B

0F: Not used

H1-05

Multi-function Input (Terminal 7)

[Terminal 7 Sel]

0F

00 to FF

Possible

B

0F: Not used

H1-06

Multi-function Input (Terminal 8)

[Terminal 8 Sel]

08

00 to FF

Possible

B

08: External baseblock

H2-01

Multi-function Output

(Terminal 9-10)

[Terminal 9 Sel]

00

00 to FF

Possible

B

00: During running

H2-02

Multi-function Output

(Terminal 25)

[Terminal 25 Sel]

06

00 to FF

Possible

B

06: Converter ready

H2-03

Multi-function Output

(Terminal 26)

[Terminal 26 Sel]

0A

00 to FF

Possible

B

0A: Duirng MCON

H4-01

Multi-function Monitor AO

(terminal 21)

[Terminal 21 Sel]

07

0 to 50

Possible

B

07: Power at power supply side

H4-02

Gain (Terminal 21)

[Terminal 21 Gain]

1.00

-300.00 to

300.00

Possible

B

H4-03

Bias (Terminal 21)

[Terminal 21 Bias]

0

-32768 to

32767

Possible

B

H4-04

Multi-function Monitor AO

(Terminal 23)

[Terminal 23 Sel]

05

0 to 50

Possible

B

05: Current at power supply side

H4-05

Gain (Terminal 23)

[Terminal 23 Gain]

1.00

-300.00 to

300.00

Possible

B

H4-06

Bias (Terminal 23)

[Terminal 23 Bias]

0

-32768 to

32767

Possible

B

H4-07

Analog Output Signal Polarity

Selection

[AO Level Select]

1

0, 1

Possible

B

0: Without sign
1: With sign

L2-01

Momentary Power Loss

Detection

[PwrL Selection]

0

0 to 2

B

0: Fault
1: Operation continues within

power loss ridethrough time

2: Operation continues if control

power supply is hold.

Note: Even if L2-01 is set to 1 or

2, the VS-656DC5 may
detect a fault if momentary
power loss occurs during
regeneration.

L2-02

Momentary Power Loss

Ridethru Time

[PwrL Ridethru t]

1.0

0.0 to 2.0 s

B

L2-05

Undervoltage Detection Level

[PUV Det Level]

190

150 to 210 V

Possible

A

For 400 V class, doulbe the set-
ting.

L3-04

Operation Selection at Input OL

(OL1) Operation

[OL1 Time Delay]

1

0, 1

B

0: Continues operation.
1: Stops operation.

(cont’d)