Appendix A CONSTANTS LIST

E-51

U1-10

Input Terminal Status

[Input Term Sts]

Q

Shows input ON/OFF status.

*1: Can be selected by H1-XX.

• Output signal level at multi-function analog output: Dis-

abled.

U1-11

Output Terminal Status

[Output Term Sts]

Q

Shows output ON/OFF status.

*2: Can be selected by H2-XX.

• Output signal level at multi-function analog output: Dis-

abled.

U1-12

Operation Status

[Drive Ope Sts]

Q

VS-656DC5 operating status

• Output signal level at multi-function analog output: Dis-

abled.

U1-13

Cumulative Operation Time

[Elapsed Time]

1 H

Q

• Output signal level at multi-function analog output: Dis-

abled.

U1-14

Software No.

[FLASH ID]

B

(Manufacturer's ID number)

U1-17

Input Power Factor

[Power Factor]

1%

B

• Output signal level at multi-function analog output

10 V: 100%
(0 to +10 V output)

U1-18

Effective Current Reference

[Real Current]

0.1%

B

• Output signal level at multi-function analog output

10 V: Rated current
(0 to +10 V output)

U1-19

Ineffective Current Reference

[Reactive Current]

0.1%

B

• Output signal level at multi-function analog output

10 V: Rated current
(0 to +10 V output)

(cont’d)

Constant No.

Name

[Display]

Unit

Access

Level

Remarks

= 00000000

1: RUN-SB (terminal 1) ON
1: STOP (terminal 2) ON
1: External fault (terminal 3) ON

*1

1: Fault reset (terminal 4) ON

*1

1: Not used (terminals 5 to 7) ON

*1

1: External baseblock (terminal 8) ON

*1

= 00000000

1: Running (terminals 9-10) ON

*2

1: CREADY (terminals 25 to 27) ON

*2

1: During MCON (terminals 26-37) ON

*2

1: Not used (always 0)
1: Fault output (terminals 18/19-20) ON

= 00000000

1: Running
1: Not used (always 0)
1: Reset input ON
1: Not used (always 0)
1: VS-656DC5 ready
1: Minor fault detected
1: Major fault detected