A.2 constant list other than monitor constants – Yaskawa Varispeed-656 DC5 User Manual

Page 64

Advertising
background image

E-54

A.2

Constant List Other Than Monitor Constants

Constant

No.

Name

[Display]

Initial

Value

Setting

Range

Change

during

Operation

Access

Level

Remarks

A1-00

Language selection for Digital

Operator display

[Select Language]

1

0, 1

Q

0: English
1: Japanese

A1-01

Constant access level

[Access Level]

2

0 to 9999

Possible

Q

0: Monitoring only
2: Quick-start (Q)
3: Basic (B)
4: Advanced (A)

A1-03

Initialize

[Init Parameters]

0000

0000 to 9999

Q

2220: Initializes using the User
Constants.

A1-04

Password 1 (Input)

[Enter Password]

0

0000 to 9999

Q

A1-05

Password 2 (Setting)

[Select Password]

0

0000 to 9999

B1-01

Voltage Reference Method

Selection

[Reference Source]

0

0

1 cannot be

set.

Q

0: Digital Operator

B1-02

Operation Method Selection

[Run Source]

1

0, 1

Q

0: Digital Operator
1: Control circuit terminals

B1-04

PRG Mode Run Command

Selection

[RUN CMD at PRG]

0

0, 1

A

0: Disabled
1: Enabled

B1-06

Read Sequence Input Twice

[Cntl Input Scans]

1

0, 1

A

0: Two scans every 3 msec
1: Two scans every 5 msec

C1-01

Acceleration Time

[Accel Time ]

10.0

0.0 to 6000.0

s

Possible

Q

C1-02

Deceleration Time

[Decel Time]

10.0

0.0 to 6000.0

s

Possible

Q

C5-01

AVR Proportional (P) Gain

[AVR P Gain]

20.00

1.00 to
300.00

Possible

B

C5-02

AVR Integral (I) Time

[AVR I Time]

0.500

0.000 to

10.000 sec

Possible

B

D1-01

Voltage Reference

[Voltage Command]

Refer to

Remarks.

300 to 340 V

(200 V class)

600 to 680 V

(400 V class)

Possible

Q

330 (200 V class), 660 (400 V
class)

F1-10

Excessive Frequency Deviation

Detection Level

[FDEV Detect Level]

3.0

1.0 to 10.0

Hz

A

F1-11

Excessive Frequency Deviation

Detection Delay Time

[FDEV Detect Time]

70.0

0.0 to 255.0

ms

A

H1-01

Multi-function Input (Terminal 3)

[Terminal 3 Sel]

24

00 to FF

Possible

B

24: Coasting to stop

H1-02

Multi-function Input (Terminal 4)

[Terminal 4 Sel]

14

00 to FF

Possible

B

14: Fault reset

H1-03

Multi-function Input (Terminal 5)

[Terminal 5 Sel]

0F

00 to FF

Possible

B

0F: Not used