3 WIRING

E-27

„

Closed-loop Connector Sizes

Determine the wire size for the main circuit so that line voltage drop is within 2 % of the rated voltage.
Line voltage drop is calculated as follows:
(If there is a possibility of excessive voltage drop, use a larger wire suitable to the required length.)

Line voltage drop (V) = 3

× wire resistance (Ω/km) × wire length (m) × current (A) × 10

-3

Table 5 Closed-loop Connector Sizes (JIS C 2805) (For 200 V/400 V Classes)

Wire Size (mm

2

)

Terminal Screw

Closed-loop Connector

Size (mm

2

)

0.5

M3.5

M4

1.25 to 3.5

1.25 to 4

0.75

1.25

2

M4

2 to 4

M5

2 to 5

3.5

M4

3.5 to 4

M5

3.5 to 5

5.5

M4

5.5 to 4

M5

5.5 to 5

8

M5

8 to 5

M6

8 to 6

14

M6

14 to 6

22

M8

22 to 8

38

M8

38 to 8

38

M10

38 to 10

60

60 to 10

80

80 to 10

100

100 to 10

100

M12

100 to 12

150

150 to 12

200

200 to 12

NOTE