Closed-loop connector sizes – Yaskawa Varispeed-656 DC5 User Manual
Page 37

3 WIRING
E-27
Closed-loop Connector Sizes
Determine the wire size for the main circuit so that line voltage drop is within 2 % of the rated voltage.
Line voltage drop is calculated as follows:
(If there is a possibility of excessive voltage drop, use a larger wire suitable to the required length.)
Line voltage drop (V) = 3
× wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
Table 5 Closed-loop Connector Sizes (JIS C 2805) (For 200 V/400 V Classes)