Related Drive Parameters

The following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be found

in the drive manual.
Confirm proper setting of the parameters in

Table 6

before starting network communications. After changing parameter

settings, cycle power to the drive for the new settings to take effect.

Table 6 Related Parameters

No.

(Addr.

Hex)

Name

Description

Values

b1-01

(0180)

<1>

Frequency Reference Selection

1

0: Digital operator

1: Analog input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse input (terminal RP)

Default: 1

Range: 0 to 4

b1-02

(0181)

<1>

Run Command

Selection 1

0: Digital operator

1: Digital input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

Default: 1

Range: 0 to 3

F6-01

(03A2)

Communications Error

Operation Selection

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.

1: Coast to stop

2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only

<2>

4: Alarm (d1-04)

<3>

5: Alarm Ramp to Stop

<3>

Default: 1

Range: 0 to 5

F6-02

(03A3)

External Fault from Comm.

Option Detection Selection

1: Detection during run only

Default: 0

Range: 0, 1

F6-03

(03A4)

External Fault from Comm.

Option Operation Selection

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.

1: Coast to stop

2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only

<2>

Default: 1

Range: 0 to 3

F6-07

(03A8)

Multi-Step Speed Enable/

Disable Selection when

NefRef/ComRef is Selected

0: Multi-step reference disabled (same as F7)

1: Multi-step reference enabled (same as V7)

Default: 1

Range: 0, 1

F6-08

(036A)

<4>

Reset Communication

Parameters

0: Communication-related parameters (F6-oo/F7-oo) are not reset when

the drive is initialized using A1-03.

1: Reset all communication-related parameters

(F6-oo/F7-oo) when the drive is initialized using A1-03.

Default: 0

Range: 0, 1

F6-14

(03BB)

bUS Error Auto Reset

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

F7-01

(03E5)

<5>

IP Address 1

Sets the most significant octet of network static IP address.

Default: 192

Range: 0 to 255

F7-02

(03E6)

<5>

IP Address 2

Sets the second most significant octet of network static IP address.

Default: 168

Range: 0 to 255

F7-03

(03E7)

<5>

IP Address 3

Sets the third most significant octet of network static IP address.

Default: 1

Range: 0 to 255

F7-04

(03E8)

<5>

IP Address 4

Sets the fourth most significant octet of network static IP address.

Default: 20

Range: 0 to 255

F7-05

(03E9)

Subnet Mask 1

Sets the most significant octet of network static Subnet Mask.

Default: 255

Range: 0 to 255

F7-06

(03EA)

Subnet Mask 2

Sets the second most significant octet of network static Subnet Mask.

Default: 255

Range: 0 to 255

F7-07

(03EB)

Subnet Mask 3

Sets the third most significant octet of network static Subnet Mask.

Default: 255

Range: 0 to 255

F7-08

(03EC)

Subnet Mask 4

Sets the fourth most significant octet of network static Subnet Mask.

Default: 0

Range: 0 to 255

F7-09

(03ED)

Gateway Address 1

Sets the most significant octet of network Gateway address.

Default: 192

Range: 0 to 255

6 Related Drive Parameters

20

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual