Digital Operator Display

Fault Name

oFA03

Option Card Fault (port A)
Option card self-diagnostic error

oFA04

Option Card Fault (port A)
An error occurred attempting to write to the option card memory.

to

oFA30 to oFA43

Option Card Fault (port A)
Communication ID error

Cause

Possible Solution

Option card or hardware is damaged.

Replace the option card. Contact Yaskawa for consultation.

n

Minor Faults and Alarms

Digital Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solutions

Minor Fault

(H2-oo = 10)

Communications wiring is faulty, there is a

short circuit, the wiring is incorrect, or the

connections are poor.

• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.

YES

Programming error on the master side.

Check communications at start-up and correct programming errors.

Communications circuitry is damaged.

• Perform a self-diagnostics check.
• If the problem continues, replace the control board or the entire drive. Contact

Yaskawa for instructions on replacing the control board.

n

bUS Fault Tolerance

bUS Fault Auto-Restart

Parameter F6-14, bUS Fault Auto Reset Select, will appear when the option is installed.
Setting F6-14 = 0 (Disabled) or F6-01 = 3 or greater (Alarm only) will not affect standard default drive behavior.
Setting F6-14 = 1 (Enabled) AND F6-01 < 3 (Fault) will cause the following operation: The bUS fault occurs after the F7-16

delay and the Run command is removed from the drive. Then the option throws a bUS fault to the drive. When the condition

is removed, the option commands a fault reset and returns control of the drive to the Modbus TCP/IP network.

Note:

The option will only read parameter F6-01 and F6-14 from the drive during power-up.

bUS Fault Delay

Parameter F7-16, Communications Loss Detection Time Delay, will appear when the option is installed.
The setting value of F7-16 is the length of time that the option will delay sending the bUS fault to the drive.
The status LEDs on the option are not affected by the delay time set in F7-16; the LEDs will indicate the bUS condition

immediately.

Note:

The option will only read parameter F7-16 from the drive during power-up.

u

Option Error Codes

n

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in

Table

40

.

Table 40 Option Fault Monitor Descriptions

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults

Force Fault

EF0

3

Network sent a message to force this node to the fault

state.

Connection Timeout

BUS ERROR

1101

The control connection timed out.

10 Troubleshooting

46

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual