Message content, Modbus tcp/ip option function details – Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual

Page 26

Advertising
background image

n

H5-11 and the Enter Command

H5-11 Settings

H5-11 = 0

H5-11 = 1

Drive being replaced

G7, F7

V7

How parameter settings are enabled When the Enter command is received from the master.

As soon as the value is changed.

Upper/lower limit check

Upper/lower limit check is performed taking the settings

of related parameters into account.

The upper/lower limit of the changed parameter is

checked only.

Default value of related parameters Not affected. The settings of related parameters remain

unchanged. They must be changed manually if needed.

The default settings of related parameters are changed

automatically.

Error handling when setting

multiple parameters

Data is accepted even if one setting is invalid. The invalid

setting will be discarded. No error message occurs.

Error occurs if only one setting is invalid. All data sent

are discarded.

u

Message Content

The data section of the Modbus packet contains the Modbus message. In this data section, the master sends commands to the

slave, and the slave responds. The message format is configured for both sending and receiving as shown below, and the length

of data packets depends on the command (function) content.

SLAVE ADDRESS
FUNCTION CODE

DATA

ERROR CHECK

n

Unit Identifier

This field is used for intra-system routing purposes. It is typically used to communicate to a Modbus+ or a Modbus serial line

slave through a gateway between an Modbus TCP/IP network and a Modbus serial line. This field is set by the Modbus master

in the command and must be returned with the same value in the response by the slave. This is sometimes referred to as the

Unit ID. A drive using the option has no gateway functionality.

n

Function Code

When sent by the master, this field identifies the command to be undertaken by the slave. It also identifies the format for the

DATA section of the message. The slave normally echoes this command back to the master in its response message. When

the most significant bit of this field is set in the response message, it signals an error condition has occurred.

n

Data

This field contains multiple bytes of varying length based upon the Function Code for commands and based upon the results

of the command in the response. When sent by the master, this field contains details of the command that the slave will require

to carry out the function. When sent by the slave, this field contains details of the response and sometimes error information.

u

Modbus TCP/IP Option Function Details

n

Read Multiple Registers 03 (03 H)

This function code is used to read the contents of a contiguous block of registers. The command specifies the starting register

and the number of registers. The normal response packs two bytes per register. For each register in the response, the first byte

contains the most significant bits and the second byte contains the least significant bits.

Table 11 Read Multiple Registers Command

Description

Byte

Data (Hex)

Slave Address

1

00 to FF

Function Code

1

03

Starting Register

2

0000 to FFFF

Quantity of Registers

2

N

<1>

<1> N = Quantity of Registers (range is 1 - 16)

Table 12 Read Multiple Registers Response

Description

Byte

Data (Hex)

Slave Address

1

00 to FF

Function Code

1

03

7 Modbus TCP/IP Messaging

26

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual