Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual

Page 28

Advertising
background image

Table 17 Table 19 Write Single Register Command

Description

Byte

Data (Hex)

Slave Address

1

00 to FF

Function Code

1

06

Register Address

2

0000 to FFFF

Register Value

2

0000 to FFFF

Table 18 Write Single Register Response

Description

Byte

Data (Hex)

Slave Address

1

00 to FF

Function Code

1

06

Register Address

2

0000 to FFFF

Register Value

2

0000 to FFFF

Table 19 Write Single Register Error Response

Description

Byte

Data (Hex)

Slave Address

1

00 to FF

Error Code

1

86

Exception Code

1

Refer to Modbus TCP/IP Exception Codes

on page 31

for details.

Examples of Register Write Command

Table 20

lists command examples when writing register value 0003H to register address 0001H in a drive with the slave

address (unit identifier) 01H.

Table 21

shows examples of responses indicating that the write command has been executed successfully. The command

specifies the value and the register address to write to.

Table 22

shows examples of an error response when writing to a register. The exception code is 21H (indicating an invalid

value).

Table 20 Example Write Single Registers Command

Description

Data (Hex)

Slave Address

01

Function Code

03

Register Address

Upper

00

Lower

01

Register Value

Upper

00

Lower

03

Table 21 Example Write Single Register Response

Description

Data (Hex)

Slave Address

01

Function Code

06

Register Address

Upper

00

Lower

01

Register Value

Upper

00

Lower

03

Table 22 Example Write Single Register Error Response

Description

Data (Hex)

Slave Address

01

Error Code

86

Exception Code

21

7 Modbus TCP/IP Messaging

28

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual