Enter command types, Enter command settings when upgrading the drive – Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual

Page 25

Advertising
background image

Address

(hex)

Drive

Register

(hex)

Description

Bit

Description

200B

C2

Error Signal 3

0

MEMOBUS/Modbus Communication Error (CE)

1

Option Communication Error (bUS)

2

Reserved

3

Reserved

4

Control Fault (CF)

5

Zero Servo Fault (SvE)

5

Reserved

6

Option External Fault (EF0)

7

PID Feedback Loss (FbL)

8

Undertorque Detection 1 (UL3)

9

UL4 Undertorque Detection 2 (UL4)

A

High Slip Braking Overload (oL7)

B

Reserved

C

Reserved

D

Reserved

E

Reserved

F

Hardware Fault (includes oFo)

200C

4E

Terminal A1 Input Level Monitor (U1-13)

200D

49

Digital Input Terminal Status (U1-10)

200E

50

Terminal A3 Input Level Monitor (U1-15)

200F

F1

PG Count Channel 2

2010

4D

Drive Software Number (Flash) (U1-25)

u

Enter Command Types

The drive supports two types of Enter commands as shown in

Table 10

. An Enter command is enabled by writing 0 to register

number 0900H or 0910H. These registers can be written to only. An error will occur if the user attempts to read from these

registers.

Table 10 Enter Command Types

Register No.

Description

0900H

Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at the same time. Parameter

changes remain even if the power supply is cycled.

0910H

Writes data in the RAM only. Parameter changes are lost when the drive is shut off.

Note:

1. Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the EEPROM too often. The Enter

command registers are write-only. Consequently, if these registers are read, then the register address will be invalid (Error code: 02H).

An Enter command is not required if reference or broadcast data are sent to the drive.

2. Parameter data cannot be written to EEPROM during undervoltage, even using 0900H.
3. If undervoltage occurs when a making several parameter changes issued with a single ENTER command, the writing process may be

aborted before all of the new changes have been written. Because all of the data has not yet been written, the EEPROM data error

“CPF06” will be displayed the next time power to the drive is cycled. To prevent this problem, wait approximately 5 seconds after

issuing the ENTER command before shutting off drive power.

u

Enter Command Settings when Upgrading the Drive

When replacing earlier Yaskawa drive models with a V1000 and keeping the MEMOBUS/Modbus communications settings,

parameter H5-11 needs to be set in accordance with how the Enter command functions in the older drive. H5-11 determines

if an Enter command is needed to activate parameter changes in the drive.
• Set parameter H5-11 to 0 when upgrading from a G7 or F7 series drive to V1000-Series drive.
• Set parameter H5-11 to 1 when upgrading from a V7 series drive to V1000-Series drive.

7 Modbus TCP/IP Messaging

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual

25

Advertising
This manual is related to the following products: