Troubleshooting, Drive-side error codes, 10 troubleshooting – Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual

Page 45

Advertising
background image

10

Troubleshooting

u

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed below. Refer

to the drive manual for additional error codes that may appear on the drive digital operator.

n

Faults

Both bUS (Option Communication Error) and EF0 (Option Card External Fault) can appear as an alarm or as a fault. When a

fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
• Is the option properly installed?
• Are the communication lines properly connected to the option? Are the wires loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?

Digital Operator Display

Fault Name

bUS

Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the Run command or frequency reference is assigned to the option (b1-01 = 3 or

b1-02 = 3).

Cause

Possible Solution

Master controller (PLC) has stopped

communicating

• Check that power is supplied to the PLC
• Check that PLC is not in program mode

Communication cable is not connected

properly

• Check for faulty wiring
• Correct any wiring problems

A data error occurred due to noise

• Check the various options available to minimize the effects of noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to the contactor coil
• Make sure the cable used meets requirements
• Make sure the option ground wire is connected between option FE terminal and the drive ground

terminal connected to earth ground

Option is damaged

If there are no problems with the wiring and the error continues to occur, replace the option.

Digital Operator Display

Fault Name

EF0

Option Card External Fault
The alarm function for an external device has been triggered.

Cause

Possible Solutions

An external fault was received from the PLC

and F6-03 is set to a value other than 3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

Digital Operator Display

Fault Name

oFA00

Option Card Connection Error at Option Port CN5-A
The option card is incompatible with the drive.

Cause

Possible Solution

Digital Operator Display

Fault Name

oFA01

Option Card Fault
Option not properly connected

Cause

Possible Solution

The option card connection is faulty

• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.

10 Troubleshooting

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual

45