Write single register 06 (06 h) – Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual

Page 27

Advertising
background image

Description

Byte

Data (Hex)

Number of Data Bytes

1

2 x N

<1>

Register Values

N

<1>

x 2

Values contained in slave registers.

<1> N = Quantity of Registers

Table 13 Read Multiple Registers Error Response

Description

Byte

Data (Hex)

Slave Address

1

00 to FF

Error Code

1

83

Exception Code

1

Refer to Modbus TCP/IP Exception Codes

on page 31

for details.

Examples of Fault Response, Read Response, and Read Multiple Registers Command

Note:

In option software version VST800380, any invalid register in the range will return an error response.

In option versions VST800381 and later, invalid registers in the range will not return an error response provided at least 1 register is valid.

Invalid registers will be set to 0 in the response.

Table 14

lists command examples to read register contents (register addresses 0020H to 0023H) from a drive with the slave

address (unit identifier) 02H.

Table 15

shows examples of responses indicating that multiple registers have been read successfully. The contents read from

0020H are 1770H, 1770H, 0109H, and 0000H.

Table 16

shows examples of an error response when reading multiple registers. The exception code is 02H (indicating a register

number error).

Table 14 Example Read Multiple Registers Command

Description

Data (Hex)

Slave Address

02

Function Code

03

Starting Register

Upper

00

Lower

20

Quantity of Registers

Upper

00

Lower

04

Table 15 Example Read Multiple Registers Response

Description

Data (Hex)

Slave Address

02

Function Code

03

Number of Data Bytes

08

Starting Register

Upper

17

Lower

70

Next Register

Upper

17

Lower

70

Next Register

Upper

01

Lower

09

Last Register

Upper

00

Lower

00

Table 16 Example Read Multiple Registers Error Response

Description

Data (Hex)

Slave Address

02

Error Code

83

Exception Code

02

n

Write Single Register 06 (06 H)

This function code is used to write to a single register in the drive. The command specifies the address of the register to be

written and the value to write. The normal response is an echo of the request, returned after the register contents have been

written.

7 Modbus TCP/IP Messaging

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual

27