Configuration tab – Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual

Page 39

Advertising
background image

u

Configuration Tab

The Configuration tab sets web page behavior parameters. Access is restricted unless a valid password is entered.

Figure 29 Configuration Tab View

n

Security Login

Enter a valid password and click “Log in”. The button text changes to “Log out” and the status changes to “Logged in”.

Note:

The default security password is “yaskawa”.

This password can be changed in the “Change Password” section of the tab. Entering a valid password allows access to the

settings in the Configuration tab, Email Alerts tab, and the Parameter Access tab.

n

Change Password

To change the password, enter the new password in the “New Password:” and “Confirm Password:” text boxes then click

“Change password”. The Status display will change to “Idle” then “Changing Password” then “Password Changed”. If the

passwords in the two text boxes do not match, the Status will display “Passwords don’t match”.

n

Option Card

The values displayed in the various tabs are refreshed at the rate defined in the “Applet Refresh Rate (ms)” text box. Enter

values in the range of 1000 ms to 65.535 seconds.
Parameter Security can be enabled or disabled by clicking one of the radio buttons. When “Disabled” is selected, no password

is necessary and all functions in the web pages will be available. When “Enabled” is selected, a valid password must be entered

to edit email settings and to write parameters.

n

Email Settings

The “Email Server IP” text box must contain the IP address of the email server. The subnet address is configured in drive

parameters F7-05 through F7-08. The configured email alerts will use the server at this address when sending emails.
Enter the email server port in the “Email Port” text box.
The value in the “From Email Address” text box identifies the origin of the email alerts to the recipient.
Click “Submit Email Parameters” to save the email settings to the option.
Click “Save Configuration Parameters to Flash” to save the entered values from this tab into non-volatile memory. These

values will then be remembered after cycling power.

n

General Settings

Click “Save Options Card Parameters” to save the Applet Refresh Rate and the Parameter Security settings to the option.

8 Web Interface

YASKAWA SIEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Technical Manual

39

Advertising
This manual is related to the following products: