PS69-DPS ♦ CompactLogix or MicroLogix Platform

RSLogix Example Program

Profibus DP Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 51 of 108

May 9, 2014

Configuration
word

Data
type

Low/High
Byte

Description

Configured
values

Explanation

9

INT

LOW Byte

Module 2 Type

5

Module 2 Type:
Input Word with consistency

HIGH Byte

Module 2 Length

1

Module 2 Length: 2 (word)

10

INT

LOW Byte

Module 3 Type

6

Module 3 Type:
Output Byte with consistency

HIGH Byte

Module 3 Length

3

Module 3 Length: 4 (byte)

11

INT

LOW Byte

Module 4 Type

7

Module 4 Type:
Output Word with consistency

HIGH Byte

Module 4 Length

1

Module 4 Length: 2 (word)

...

...

...

...

31

INT

LOW Byte

Module 24 Type

0

HIGH Byte

Module 24 Length

0

The parameter "ForceUserConfiguration" is initialized with 0. If you want to
activate the pre-defined modules set this parameter to 1. When this parameter is
active the master configuration has to match exactly with this configuration
otherwise the slave will not start the communication with the master.

The parameter busaddress is independent from the parameter
"ForceUserConfiguration". This parameter will be active, if the rotary address
switches of the module are set to "00".